What are the employers’ responsibilities for the storage of compressed gas cylinders?
Employers must make sure the following are put in place when compressed gases are used or stored at the workplace: Employers must:
- context Develop and implement a safe operating procedure for the safe handling and storage of compressed gas cylinders. The safe operating procedure must be prepared by a safety technical specialist and be based on the hazards of the gases present when used, stored, or handled. Include a description that outlines a gas cylinder is considered to be “in storage” versus “in use.”
- context Make sure the workers receive the necessary training, including WHMIS.
- context Keep an accurate and up-to-date inventory of all cylinders.
Control the maximum quantities of gases allowed on site as per legislative requirements.
- context Make sure fuel gas cylinders are not stored in cabinets, whether totally enclosed or vented. When security is a concern for mobile gas welding systems, a screened cage can be used to contain the cylinders; however, at least two sides of the cage must have an 80% or greater area, which allows for airflow.
- context Monitor for flammable and oxygen gas levels in the storage area.
Know the local requirements for firewall specifications and separation distances for incompatible gases.
- context Make sure compressed gas containers and systems are secured and protected against physical damage and tampering.
- context Select outdoor storage areas that are well-drained with a concrete or other non-combustible platform. Asphalt of hydrocarbon-based paving material should not be used for the storage of oxidizing gases. In addition, the area needs to be located where the cylinders will not be exposed to humid conditions.
- context Make sure the storage area location meets the jurisdiction’s distance requirements from forested areas. Make sure the surrounding area is maintained so that there is no grass, weeds, brush, or other vegetation within the specified distance by the jurisdiction. Generally, this distance is six metres.
- context Make sure that indoor storage gas rooms are constructed according to the specifications in the building, electrical, and fire codes.
- context Post "no smoking" signs in the indoor and outdoor storage areas.
- context Establish and post a maximum use temperature of less than 48.9°C (120°F) and a maximum temperature for indoor and outdoor storage of less than 51.7°(125°F).
- context Consider setting up the cylinder storage so that each cylinder can be secured separately to prevent other cylinders from falling when one of them is removed from storage.
What are the workers’ responsibilities when storing compressed gas cylinders?
Note that when a single cylinder of oxygen and fuel gas are attached to a cylinder cart/trolly or secured to a wall or column at a workstation, this situation is not considered storage, and the cylinders do not necessarily need to be separated by distance or a barrier.
- context Store compressed gas cylinders according to your organization’s safe operating procedure.
- context Make sure you have received the necessary training, including WHMIS. Only trained workers are allowed to handle compressed gases.
- context Do not smoke in compressed gas storage areas (indoors or outdoors). Note that oxygen alone will not combust, but it will vigorously support and accelerate combustion, causing flammable materials to burn with great intensity. Oil or grease in the presence of oxygen can ignite readily and burn violently.
- context Wear the required (if any) personal protective equipment (PPE) and use only the appropriate equipment (e.g., carts, tools, fittings, and equipment).
- context Before using or storing the cylinders, make sure they are properly identified or labelled and that they are in good condition. For cylinders that are not in good condition (e.g., the valve is hard to operate or there is visible damage), place a warning label on it, and report it to the supervisor to have it removed from service.
- context Store cylinders in a clearly identified, dry, well-ventilated storage area that is not exposed to heat or the direct rays of the sun, and away from doorways, aisles, elevators, gangways, stairs, electrical outlets, etc.
- context Identify empty cylinders with a tag and store them separately from full cylinders.
- context Store cylinders, both empty and full, in the upright position (unless otherwise instructed).
- context During storage, close the cylinder valves with the protective caps or a specific protective device in place.
- context Secure cylinders with an insulated chain or non-conductive belt to protect cylinders from falling or becoming damaged.
- context When storing outside, make sure the cylinders are stored in the designated storage area. Place the cylinders on a raised concrete pad (or other non-combustible platform) or noncombustible rack inside a secure designated area that is fenced in. The platform should be designed to prevent the cylinders from corroding from contact with ground, ice, snow, water, salt, and high temperatures.
- context Unless otherwise instructed, when storing indoors, store the cylinders only in rooms that are specifically designated. These rooms must meet specific design, electrical, and ventilation requirements as outlined in the fire, electrical and building codes.
- context Protect cylinders from falling. Secure the cylinders according to the instructions in the safe operating procedure. Tip! Securing each cylinder separately prevents other cylinders from falling when one of them is removed from storage.
- context Store acetylene and liquefied gas cylinders valve end up. Close the valve and keep the protective device in place.
- context Cylinders must also be separated away from flammable products and from materials that easily ignite (such as wood, paper, oil, grease, etc.). Unless otherwise specified in the safe operating procedure, the general recommendation is to store oxygen cylinders and fuel gas cylinders separately when "not in use." This method applies to indoor and outdoor storage.
- context Separate oxygen from fuel gas cylinders by at least 6.1 m (20 ft), or by a wall at least 1.5 m (5 ft) high with a minimum half-hour fire resistance.
- context The temperature of the storage area should not be above 51.7°(125°F)
- context Make sure there are "no smoking" signs in the area.
- context If oxygen cylinders are stored in an outdoor acetylene generator house, the cylinders must be separated from the generator and carbide storage room by a non-combustible barrier with a fire-resistance rating of at least 1 hour, that has no openings and is gas tight.
What welding gases can be stored together?
The following table lists storage recommendations. Always follow the instructions on the safety data sheet or those provided by the manufacturer.
Inert gases
No separation is required.
Can be stored together
No separation is required.
Can be stored together
Fuel gases
(e.g., propane, propylene, acetylene, or hydrogen)
The National Fire Code does not require separation.
Good industry practices (e.g., the Canadian Gas Association) recommend separation.
Generally, a minimum of 3 metres separation is recommended.
The National Fire Code does not require separation.
Good industry practices (e.g., the Canadian Gas Association) recommend separation.
Generally, a minimum of 3 metres separation is recommended.
Inert gases
(e.g., argon, helium, or nitrogen)
No separation is required.
Can be stored together
The National Fire Code does not require separation.
Good industry practices (e.g., the Canadian Gas Association and other authorities) recommend separation.
Generally, a minimum of 3 metres separation is recommended.
Not applicable
No separation is required.
Can be stored together
The National Fire Code does not require separation.
Good industry practices (e.g., the Canadian Gas Association) recommend separation.
Generally, a minimum of 3 metres separation is recommended
No separation is required.
Can be stored together
Group carbon dioxide gases together.
- context Oxygen | Group oxygen gas cylinders together. | Separate at least 6.1 m (20 ft), or by a wall at least 1.5 m (5 ft) high with a minimum half-hour fire resistance.
- context Separate at least 6.1 m (20 ft) or by a wall at least 1.5 m (5 ft) high with a minimum half-hour fire resistance. | Group fuel gas cylinders together.
- context Group inert gases together.
- context Carbon dioxide
How should cylinders be moved around a facility or within the company’s property?
NOTE: Requirements for moving cylinders within the organization’s facility or property and those intended for transportation on public throughways are not the same.
DO NOT
- context Check the instructions in the safe operating procedure for the type of equipment needed.
- context Close the valve before moving.
- context Keep valve protection caps in place and hand tightened when not in use.
- context To close the cylinder valves, remove the regulator, replace the valve protection cap and hand tight before moving a cylinder.
- context Move cylinders with appropriate trolleys and secure the cylinders in an upright position.
- context Use proper lifting cradles or a suitable platform when hoisting cylinders by a crane, derrick, or other hoisting mechanism.
- context Secure cylinders in an upright position when cylinders are transported by motor vehicle. Close the value and use protective devices.
- context Cylinders that need to be moved to different floors in a building must be transported in service elevators that are ventilated.
- context Do not lift a cylinder by the valve cap. Never sling with ropes or chains, or lift with electromagnets.
- context Do not drag, slide, or drop cylinders. Do not roll on their sides. They can be rolled for short distances on their base.
- context Do not allow the cylinders to strike each other with force.
- context Do not place cylinders on their sides as rollers to move equipment.
- context Do not lay acetylene cylinders on their sides. If an acetylene tank has unintentionally been left on its side, set it upright for at least one hour before it is used.
- context Do not try to refill a cylinder or mix gases in a cylinder.
How do I transport cylinders on public roadways?
Before any vehicle equipped with a welding gas system is operated on public roadways or parked on publicly accessible property, the employer must make sure the welding system (which includes the compressed gases) is transported in compliance with the Transportation of Dangerous Goods Act and regulations and the applicable highway traffic act.
Some of the requirements are:
- context Whenever a mobile oxygen-fuel gas welding system is assembled as a cutting/welding or heating unit, an individual capable of competently operating the equipment must accompany the vehicle.
- context The regulators and hose must be disconnected from the cylinders and placed in storage.
- context On all cylinders, the valves shall be closed, and if the cylinders are designed to have protection caps, the protection caps must be in place.
- context Transport cylinders in a suitably ventilated vehicle, ideally an open or flatbed truck.
- context Make sure the cylinders are properly restrained and valves are protected during transport.
- context Never transport gas cylinders in passenger vehicles.