Industrial Ventilation - 1. Introduction

What is covered in this document? This document is an introduction to industrial ventilation.

What is covered in this document?

This document is an introduction to industrial ventilation. It is part of a series of documents on this topic. The above documents do not cover indoor air quality and general ventilation as used in offices, homes, and other non-industrial settings. Please see the OSH Answers document Indoor Air Quality - General for more information.

What is industrial ventilation?

Why have an industrial ventilation system?

Ventilation is considered an "engineering control" to remove or control contaminants released in indoor work environments. It is one of the preferred and more effective ways to control employee exposure to contaminants released by a process into the air. Other ways to control contaminants include:

What is the purpose of a ventilation system?

There are four purposes of ventilation:

What are the parts of an industrial ventilation system?

An industrial ventilation system has two main parts: a fresh air supply system and an exhaust system. In general, the supply system is a heating, ventilation, and air-conditioning system (HVAC) and consists of: The exhaust system consists of: The Industrial Ventilation series of documents discuss these elements of the exhaust system.

What are the basic types of ventilation systems?

What are the main features of dilution ventilation?

Dilution ventilation supplies and exhausts large amounts of air to and from an area or building. It usually involves large exhaust fans placed in the walls or roof of a building. It is used to help prevent the buildup of nuisance odours, carbon dioxide, etc. Dilution ventilation controls pollutants generated at a worksite by ventilating the entire workplace. The use of dilution ventilation distributes pollutants, to some degree, throughout the entire worksite and could therefore affect persons who are far from the source of contamination. Dilution ventilation can be made more effective if the exhaust fan is located close to exposed workers and the makeup air is located behind the worker so that the contaminated air is drawn away from the worker's breathing zone. See Figures 1 to 4 for examples of better ventilation system layouts and Figure 5 for poor dilution ventilation design. When used to control chemical pollutants, dilution may be limited to situations where: It is, therefore unusual to recommend the use of dilution ventilation for the control of chemical substances except in specific cases. Figure 1 Figure 2 Figure 3 Figure 4 Figures 1 to 4: Examples of recommended dilution ventilation layouts Figure 5 Example of dilution ventilation layout that is not recommended

What are the limitations of dilution ventilation?

As a method for protecting workers, it is important to know that dilution ventilation: As a general note, the air or "volumetric" flow rate of dilution ventilation depends largely on how fast the contaminant enters the air as well as the efficiency of the fresh air and workroom air mixing process. It is common to use "floor" or "desk" fans as a method of ventilation or to provide comfort. Be aware that these fans typically blow the contaminant around the work area without effectively controlling it. Opening doors or windows can be used as dilution ventilation, but again, this method is not reliable since air movement is not controlled.

What is local exhaust ventilation?

Local exhaust systems are used to control air contaminants by trapping them at or near the source, in contrast to dilution ventilation which lets the contaminant spread throughout the workplace. Local exhaust is generally a far more effective way of controlling toxic contaminants before they reach the worker's breathing zones. This type of system is usually the preferred control method if: In a general way, a local exhaust system operates similar to a household vacuum cleaner with the hose as close as possible to the place where dirt would be created.

What are the components of local exhaust ventilation?

A local exhaust system has five basic elements (see Figure 6): Figure 6 Components of a Local Exhaust Ventilation System

How do I know which type of ventilation system is best for my workplace?

All industrial ventilation systems, when designed properly, should be able to provide long-term worker protection. The two types of ventilation, dilution and local exhaust, are compared in the following table.

In general, what are limitations of any ventilation system?

Some limitations include: The following is an example of changes that can affect how a system works: Figure 7 Addition of an exhaust duct branch When an additional exhaust branch is added to an existing duct the local exhaust ventilation will pull air into the system from the new location. This change will reduce the airflow from other locations that are further away from the exhaust fan. The airflow through the entire ventilation system will be affected. This change may result in a rapid plugging of the system and in a reduction of the exhaust airflow, throughout all ducts. The system may no longer be adequate enough to remove the contaminants it was originally designed to remove.

What should I know about make-up air?

An important and sometimes overlooked aspect of local ventilation is the need to provide enough air to replace the air that is exhausted from the workplace. If enough make-up air is not provided when large volumes of air are exhausted, the workplace becomes "starved" for air and negative pressure is created. Negative pressure in the workplace increases resistance on the ventilation system causing it to move less air. Air will also enter a building through cracks around doors or windows or other small openings to try to "equal" the rate of air being removed. The result is that workers may be exposed to cold air in the winter, and additional heating costs may occur. One way to figure out if a room is under negative pressure is to open the door about 3 millimetres and hold a smoke tube (or another object that releases a visible product in front of the opening. If the smoke is drawn into the room, the room is under negative pressure. If the smoke is pushed away from the room, the room is under positive pressure. If the smoke raises straight into the air, then the pressure in the room is the same as the outside pressure. Another way to judge if a building is under excessive negative pressure is to open a door that pushes towards outside. If you have to pull (or push from inside) hard to open the door, the building is under negative pressure (the outside pressure is higher than inside, and forces the door shut). If a building had negative pressure, a separate intake fan, located away from the exhaust fans, should be added to bring in fresh, uncontaminated air from outside. This air must be clean and heated in winter or cooled in summer, as needed. In all cases, a ventilation specialist or building engineer should be consulted to implement solutions.